Precautions for module selection-selection of module current specifications

Precautions for module selection-selection of module current specifications

  • Categories:Product Model
  • Author:
  • Origin:
  • Time of issue:2013-05-27
  • Views:0

(Summary description)Taking into account fluctuations in line voltage and load than normal at the start of its rated current is several times larger, and poor chip thyristor current impact resistance capability, we recommend that you set aside an appropriate margin should select the module current specifications. The recommended choices are as follows:

Resistive load: The nominal current of the module should be 2 times of the rated current of the load.

Inductive load: The nominal current of the module should be 3 times of the rated current of the load.

Precautions for module selection-selection of module current specifications

(Summary description)Taking into account fluctuations in line voltage and load than normal at the start of its rated current is several times larger, and poor chip thyristor current impact resistance capability, we recommend that you set aside an appropriate margin should select the module current specifications. The recommended choices are as follows:

Resistive load: The nominal current of the module should be 2 times of the rated current of the load.

Inductive load: The nominal current of the module should be 3 times of the rated current of the load.

  • Categories:Product Model
  • Author:
  • Origin:
  • Time of issue:2013-05-27
  • Views:0

Taking into account fluctuations in line voltage and load than normal at the start of its rated current is several times larger, and poor chip thyristor current impact resistance capability, we recommend that you set aside an appropriate margin should select the module current specifications. The recommended choices are as follows:

Resistive load: The nominal current of the module should be 2 times of the rated current of the load.

Inductive load: The nominal current of the module should be 3 times of the rated current of the load.

银河技术

Yinhe High-Tech Development

>   ABOUT US

 

>   PRODUCTS


>   NEWS


>   APPLICATION


>   TECHNOLOGY

 

>   CONTACT

 

CONTACT US

Address: No. 432, Linzi Avenue, Linzi District, Zibo City,

Shandong Province

MESSAGE

Username used for comment:
客户留言
Description:
验证码

Copyright 2020 Zibo Linzi Yinhe High-Tech Development Co., Ltd.    鲁ICP备12000870号    Powered by www.300.cn